Amazon's botched backup causes cloud chaos

By on
Amazon's botched backup causes cloud chaos

A series of failures in the power infrastructure supporting Amazon’s Elastic Cloud data centre in Ireland caused a rolling European service outage last week.

It comes after a major Amazon cloud  outage in May that was described as the worst in cloud computing history.

Amazon’s backup generators failed to kick in after its energy supplier suffered a massive power outage on Sunday night August 7, according to a post-incident report.

Power was lost to almost all EC2 instances in Amazon’s European Western zone, RDS database instances, 58 per cent of its Elastic Block Storage volumes and its EC2 networking gear which connected that zone to the internet. 

The failures were traced to Amazon’s Programmable Logic Controllers, which were meant to switch electrical load to backup generators. 

The PLCs failed after detecting “a large ground fault”, similar to what happens when a electrical wire becomes earthed.

They activated some backup generators but left the burden of running its cloud largely on UPS batteries, which “quickly drained”, Amazon said.

Amazon had since added more redundancy and isolation to its PLCs “so they are insulated from other failures” and was preparing a “cold, environmentally isolated” backup PLC that it planned to deploy soon. 

The power outage was initially thought to have been caused by a lightning strike but Amazon’s supplier ruled that out and was still investigating the root cause of the initial power failure.

The timing and severity of the outage hampered Amazon’s efforts to recover elastic block storage (EBS) volumes, which are normally replicated across a network of nodes that serve read-and-write requests to EC2 instances, Amazon explained.

“There were delays as this was nighttime in Dublin and the logistics of trucking required mobilising transportation some distance from the data centre," the company said.

When the outage hit, affected EBS nodes attempted to mirror across available nodes within the region, but many nodes were unable to complete the process before running out of capacity, causing “a number” of customers’ volumes to become “stuck”.

"We ran out of spare capacity before all of the volumes were able to successfully re-mirror," Amazon explained.

“We brought in additional labor to get more onsite capacity online and trucked in servers from another Availability Zone in the Region." 

The worst case was for customers that concurrently lost power to EC2 instances and all nodes containing EBS volume replicas, which Amazon explained threatened to corrupt data if a volume was brought back with errors. 

In that instance, customers were forced to wait up to three days for Amazon to retrieve a snapshot of the node and transfer it to the Amazon Simple Storage Service (S3). 

“While we provided best estimates for the long-lead recovery snapshots, we truly didn’t know how long that process was going to take or we would have shared it,” Amazon explained, defending the quality of its communications with customers throughout the outage. 

Amazon planned better communications resources for customers in the future, such as visibility over their own resources.

It expected to deliver the tools for customers to see whether instances or volumes had been impaired in the “next few months”.

It also promised to provide clearer instructions on what customers should do with the recovery snapshots.

“We sometimes assume a certain familiarity with these tools that we should not.”

Amazon has offered customers running applications in the affected zone 10 days credit equal to 100 per cent of their usage of EBS Volumes, EC2 and RDS instances.

Why Amazon accidentally deleted EBS snapshots

Amazon’s devastating outage occurred just days after one of its engineers accidentally deleted a batch of EBS volume snapshots.

Amazon has revealed that it was due to a software bug affecting how Elastic Block Storage (EBS) takes and deletes snapshots.

“On August 5th, the engineer running the snapshot deletion process checked the blocks flagged for analysis before running the actual deletion process in the EU West Region.

"The human checks in this process failed to detect the error and the deletion process was executed,” it said.  

Customers that had EBS volume snapshots deleted will receive 30 days credit for their EBS usage in the region, it said. 

Got a news tip for our journalists? Share it with us anonymously here.
Copyright © iTnews.com.au . All rights reserved.